Loadcenter Main Brkr 8sps 200a
Rainproof galvanized steel enclosure. Single phase, 3 wire, insulated/bondable neutral, 8 (1") spaces, 16 circuits, 120/240 volt AC. Main breaker type BWH at 25,000 AIC. Includes feed thru lugs for both phase and neutral conductors. With hub closure plates, hubs and ground bar kit (necessary for sub-feeding) sold separately. Tin plated aluminum bus bar. Neutral is movable to other side. When bonded, unused neutral connections may be used for equipment ground protectors in service entrance application. #2 - 300 kcmil wire range. Electrostatic powder coat, baked urethane painted. Rotate 180 degrees for bottom feed; orientation of main breaker handle consistent with NEC 240-81 requirements because it operates horizontally. 14-5/16" x 25" x 5-3/16". UL Listed file E8741.
- MAIN BREAKER LOAD CENTERS
- Box Style=C3R
- Amp Rating=200
- FEED THRU LUGS
- OUTDOOR - NEMA 3R - TOP FEED
- TYPE BR - RESIDENTIAL - G60